HomeBTU
Home › HVAC Sizing › Furnace Size

Furnace Size Calculator

Find the furnace size your home needs. Furnaces are sold by input BTU, but what heats the house is the output, which depends on efficiency (AFUE). Enter your home size, state and furnace efficiency to get both.

UPDATED OCT 2026 · HEAT LOSS AT 99% DESIGN TEMPERATURE · IECC CLIMATE ZONES
Insulation
Furnace efficiency (AFUE)
Recommended furnace
80,000 BTU
input rating · 64,000 BTU/h output
HEATING LOAD

Furnace size chart

Recommended furnace input rating for a home with 8 ft ceilings and average insulation. The first figure is for an 80% AFUE furnace, the second for a 96% AFUE furnace.

Home sizeHot
IECC 1–2
Warm
IECC 3
Mixed
IECC 4
Cold
IECC 5
Very cold
IECC 6–7
1,000 sq ft40k / 40k40k / 40k40k / 40k60k / 40k60k / 60k
1,500 sq ft40k / 40k60k / 60k60k / 60k80k / 60k90k / 70k
2,000 sq ft60k / 60k70k / 60k80k / 70k100k / 80k120k / 100k
2,500 sq ft70k / 60k90k / 70k100k / 80k120k / 100k150k / 120k
3,000 sq ft80k / 70k100k / 90k120k / 100k150k / 120k2 units / 150k

Furnaces are commonly sold in 40,000, 60,000, 70,000, 80,000, 90,000, 100,000, 110,000, 120,000, 135,000 and 150,000 BTU input sizes. Some brands offer other steps.

Input vs output BTU

The number on a furnace's model tag is its input: how much fuel it burns per hour. The heat that reaches your rooms is the output, equal to input multiplied by AFUE (annual fuel utilization efficiency).

Input rating80% AFUE output92% AFUE output96% AFUE output
40,000 BTU32,00036,80038,400
60,000 BTU48,00055,20057,600
80,000 BTU64,00073,60076,800
100,000 BTU80,00092,00096,000
120,000 BTU96,000110,400115,200

This is why replacing an old 80% furnace with a 96% model often allows a smaller input size: the new unit delivers the same heat while burning less gas.

How the size is calculated

  1. Heat loss. The calculator estimates how much heat your home loses per hour on a design day, the outdoor temperature that is colder than 99% of hours in a typical year. It uses 18 BTU per sq ft in hot climates up to 38 BTU per sq ft in very cold climates, adjusted for ceiling height and insulation.
  2. Safety margin. It adds 20%, which covers morning recovery after a thermostat setback. ACCA Manual S allows furnace output up to 140% of the heating load, so a 20% margin keeps the furnace well within that limit.
  3. Input size. It divides the required output by the AFUE you choose and picks the smallest standard input size that delivers it.
Climate zoneDesign tempHeat loss BTU/sq ftWith 20% margin
Hot · IECC 1–235 °F1821.6
Warm · IECC 325 °F2226.4
Mixed · IECC 415 °F2631.2
Cold · IECC 55 °F3238.4
Very cold · IECC 6–7−10 °F3845.6

Problems with an oversized furnace

Many older homes have furnaces 50–100% larger than they need. An oversized furnace heats the house in short bursts, which causes uneven temperatures between rooms, more noise from high airflow, and more wear on the heat exchanger and igniter. It also may need larger ducts than the house has, which raises static pressure and shortens blower life.

If your old furnace kept the house warm on the coldest days without running constantly, the new one probably does not need to be bigger. A two-stage or modulating furnace runs at low output most of the winter, which reduces the downsides of a slightly large unit.

Frequently asked questions

What size furnace do I need for a 2,000 sq ft house?

In a mixed climate, an 80,000 BTU input furnace at 80% AFUE or a 70,000 BTU furnace at 96% AFUE. In a cold climate, about 100,000 BTU at 80% or 80,000 BTU at 96%.

What size furnace do I need for a 1,500 sq ft house?

Usually 60,000 BTU in warm and mixed climates and 60,000 to 80,000 BTU in cold climates, depending on efficiency.

How many BTU per square foot for a furnace?

About 22 to 46 BTU of output per square foot including a safety margin, from hot to very cold climates. In input terms at 80% AFUE that is about 27 to 57 BTU per square foot.

Is it better to have a bigger furnace?

No. A furnace that is too large short-cycles, heats unevenly and wears out sooner. Choose the smallest standard size that covers your heat loss with a modest margin.

Should my new furnace be the same size as my old one?

Not necessarily. Many older furnaces are oversized, and if you have added insulation or new windows since, your heat loss has dropped. A higher-efficiency furnace also delivers more output per BTU of input.

These results are estimates for planning. Final furnace size should come from a Manual J heat-loss calculation by a licensed contractor.